Wood I-joist

A prefabricated wood I-joist to NDS 2024 Chapter 7 with ASCE 7-22 combinations, in ASD or LRFD. An I-joist is a proprietary product: the NDS gives no values (7.2), so the calculation works from the design resistances of the product, not from stresses. It holds the APA Performance Rated I-joists (PRI) of APA Z725H-2022 Table 9, and takes values entered from a manufacturer's report.

Inputs of the I-joist

  • Joist: the APA depth and series, or the moment Mr, shear Vr, intermediate and end reactions, EI, K, the vertical load capacity, depth, flange width and flange Fc⊥ from the manufacturer. Values are at normal duration of load. K is as APA defines it: a simple span under a uniform load deflects 5wℓ⁴/384EI + wℓ²/K. A manufacturer who writes the shear term as wℓ²/8GA has K = 8 GA. The APA values come from a copy of the 2022 revision (APA's current one is March 2024): confirm them, and the product you specify.
  • Spacing and loads: area loads per square foot over the spacing and the full length, plus line and point loads with their load types. Own weight is entered (about 2.5 to 5 plf).
  • Partial loading: on by default. L, Lr and S also act on part of the spans (ASCE 7-22 4.3.3, 7.5), as on the sawn lumber beam. The APA span tables were not calculated this way: read their note on it.
  • Bearing: the lengths at the ends (at least 1-3/4 in.) and at intermediate supports (at least 3-1/2 in.; the support next to a cantilever counts as intermediate), bearing stiffeners at the ends, an end in a hanger whose sides do not reach the top flange (it needs a stiffener), load stiffeners at point loads, and the Fc⊥ of the plate. Table 9 note i limits a reaction to the bearing on the flange or the plate, whichever is smaller.
  • Lateral stability: whether the ends are held against rotation at the bearings (required, NDS 7.3.5.2), and the unbraced lengths of the top and bottom flanges. 0 = held throughout, CL = 1.0. An unbraced flange is designed as a column by itself, buckling sideways (7.3.5.3), which needs the flange's Fc and Emin from the manufacturer: the prefilled values are sawn No. 2 values and matter only where a length is entered.
  • Deflection and service: limits as span / n (APA's tables use 480 for live load; the IBC floor value is 360), creep (Kcr = 1.5, NDS 3.5.2), temperature, and the APA cantilever limits, which you can clear where you engineer the cantilever.
  • LRFD format conversion: NDS 7.3.8 takes KF from the manufacturer. 2.54 and 2.88 are prefilled, the Table 2.3.5 values for bending and shear: check them against the product report. A reaction takes the shear value, as Table 7.3.1 has φ = 0.75 for it.

Auto-design varies the depth and series from the APA table (shallowest then lowest series, or lowest stiffness that passes); the spacing when unlocked. Entered values stay as entered.

Checks performed

CheckBasis
Moment, positive and negative, with CD or KF φ λ, Ct and CLNDS 7.3, Table 7.3.1; 7.3.5.2, 7.3.5.3
Shear, no reduction near supportsNDS 7.3, 7.4.7
End reaction, interpolated by bearing length, with or without stiffeners, limited by flange or plate bearingNDS 7.4.1; APA Table 9 notes f, i
Intermediate reaction at 3-1/2 in.NDS 7.4.1; APA Table 9 note e
Minimum bearing lengthsAPA p. 8 note 7
Stiffener at a low hanger; load stiffener above 1,500 lb on the top flange, adjusted for durationNDS 7.4.2; APA p. 16
Vertical load in the plane of the joist against VLC, no duration increaseAPA Table 9 note a, p. 8 note 10
Ends held against rotationNDS 7.3.5.2
Cantilever at most 4 ft and 1/4 of the adjacent span (option)APA p. 17
Live and total deflection with bending and shear deformation, creepNDS 7.4.5, 3.5.2; APA Table 9 note h; IBC Table 1604.3 limit entered

Limitations

  • Web holes (7.4.3), notches (7.4.4), wet service (7.1.4: dry use only), pressure treatment and floor vibration are not checked.
  • Composite action with glued sheathing is not used: Table 9 is the bare joist, so spans come out shorter than the APA span tables, which assume a glued-nailed floor.
  • On a continuous joist the moments and reactions are those of a bending analysis; shear deformation is added to the deflection but does not redistribute them.
  • A wall or roof load at the end of a cantilever usually needs reinforcement: APA Tables 5 and 6 are not applied; the module warns.
  • Web and bearing values with stiffeners at intermediate supports are the manufacturer's: only the Table 9 intermediate value is used.
  • NDS 7.3.5.3 calls the flange column method "one acceptable method"; the manufacturer may have another.

Verification examples

Verification status: 22 values compared in 9 examples (5 published, 4 hand calculations from the cited equations): 22 within tolerance, 0 recorded deviations. Code basis: the provisions it uses were read in the target edition.

No free worked example of an I-joist calculation was found. The NDS has none; the APA guide gives design values and span tables only. So the module is checked three ways, and the reader should weigh them as such:

ExampleWhat it checksPublished / hand valueILX Calcs
HAND-111-7/8 in. PRI-40 at 16 in., 16 ft, D 15 + L 40 psf, ASD and LRFDHand: M' 3,545 lb-ft, V' 1,420 lb, R' 1,200 lb from Table 9; Δ by Table 9 note h; LRFD with KF φ λsame
HAND-2Snow duration, 2-7/8 in. bearingHand: R' = (1,200 + 1,420)/2 × 1.15 = 1,506.5 lbsame
HAND-3Plate bearing governs (Table 9 note i)Hand: 708.8 lbsame
HAND-4Bottom flange unbraced 6 ft (7.3.5.3)Hand: CL = Cp of the flangesame
APA-T1-1 to 3Table 1 spans less 12 in. (note b, nailed-only floor), where L/480 governsRatio of deflection to limit 1.0, 5 % band: a reverse reading, since the tables are for a composite floor and print clear spanswithin the band
APA-T1-4Table 1, 11-7/8 in. PRI-40 at 24 in., 16 ft 8 in., moment governsRatio 1.0, 5 % bandwithin the band
APA-T2-1Table 2, 14 in. PRI-50 at 24 in., two spans of 16 ft 1 in., interior reaction governsRatio 1.0, 5 % bandwithin the band

The module's table of APA values is checked by test against the printed rows. Open: the current APA revision and a product evaluation report with its KF values.