Combined footing

A rectangular footing under two columns, designed to ACI 318-19 (13.3.4 and Chapter 8) with ASCE 7-22 loads. The footing is analysed as a beam along its length under the factored net soil pressure and the column loads; the columns' transverse beams, punching and bearing are checked at each column.

Inputs of the combined footing

  • Footing: length L, width B, thickness h, soil cover and unit weights. For a uniform soil pressure under D + L the length should be twice the distance from the left end to the resultant of the column loads; the calculation suggests that length when yours differs.
  • Columns: the centre of each column from the left end (x1 < x2) and its size (c1 along L, c2 across), and the columns' concrete f'c. The columns are on the footing's centreline.
  • Column loads per column and load type, unfactored: P and the moment M in the long direction (positive moves the resultant toward the right end).
  • Soil: allowable pressure and its basis (gross or net).
  • Reinforcement: top and bottom longitudinal bars (size and number across B), transverse bottom bars (size and spacing), which bottom layer is outermost, covers; λs option (13.2.6.2 lets you neglect it).

Auto-design (editor toolbar) varies the width (1/2-ft steps), thickness (2-in. steps), longitudinal bottom and top bars and transverse bars; the length when unlocked (column positions kept). Objectives: lowest cost index (concrete, formwork, reinforcement); least concrete, then cost. Kept unless you select them: length L. Every other input is kept; see Auto-design.

Checks performed

CheckBasis
Soil bearing, resultant within the footing, net upliftLinear pressure along L (uniform, trapezoidal or triangular), 2.4.1 combinations, 13.3.1.1 and 13.3.4.3
Shear and moment along LExact for the linear net pressure; diagrams of the combination governing the negative moment
Top steel (negative moment) and bottom steel (positive moment at the column faces and overhangs)22.2 with φ by εt; As,min 8.6.1.1; tension control; spacing 8.7.2.2
One-way shear along LAt d from the column faces (13.2.7.2), Table 22.5.5.1(c)
Transverse beams under each columnWidth c1 + d/2 on each side (limited by the footing end), Pu/B over the cantilever from the column face; flexure and shear
Punching at each column22.6 with the edge (three-sided) section where the column is close to the end; moment transfer 8.4.4.2
Bearing and dowels22.8.3.2 on the footing and on each column base; 16.3.4.1 note
Minimum transverse steel, development8.6.1.1 per foot; 25.4.2.4 for the bottom, top (ψt = 1.3) and transverse bars

The drawings (screen, report, DXF and PDF sheet) show the footing plan with the two columns (marks C1, C2) and the bottom bars both ways, section A along L with the top and bottom longitudinal bars, the transverse bars at their spacing and the soil cover, the factored shear and moment diagrams along L under it, and section B across the footing at column 2. Bars are drawn over the full length as designed; cut-offs, hooks, splices and column dowels are not part of the calculation and the sheet notes say so.

Limitations

  • Rectangular footings only (no trapezoidal or strap footings); columns on the centreline; moments across the width are not entered.
  • The transverse-beam width (c1 + d/2 each side) is common textbook practice, not a code rule; confirm it against your practice.
  • Verified by hand calculation only; no published combined-footing example is on file.

Verification examples

Published worked example (backend/tests/test_verify_combined_footing.py): the free StructurePoint example that reproduces Wight, Reinforced Concrete Mechanics and Design, 7th Ed., Example 15-5 (ACI 318-14): 25 ft 4 in × 8 ft, an exterior 16 × 24 in column at the property line and an interior 24 in column 20 ft away.

ExampleWhat it checksPublishedILX Calcs
SP-CF, h = 36 inPunching vu, interior column / φvc80.2 / 164.3 psi80.2 / 164.3
SP-CF, h = 36 inPunching vu, exterior column (three-sided, γv Munb about the section centroid)192 psi191.7
SP-CFNegative moment between the columns2100 kip-ft (diagram)2112
SP-CF, h = 40 inAs,min = 0.0018 b h6.91 in²6.91
SP-CF, h = 40 inPunching vu, exterior column (deviation: the column sides are within d of the long edges, so the program also checks the section open to them, which governs)157 psi242.6

This example found an error, now fixed: the moment transferred by eccentric shear at an edge column was taken as Vu times the eccentricity of the column; it is now the moment of the column load and of the soil reaction inside the section about the section's centroid (ACI 318-19 R8.4.4.2.3), which raised vu at the exterior column from 184 to 192 psi.

Hand calculation of the default design: 21.5 ft × 7 ft × 36 in, columns at 1 ft and 17 ft.

What it checksHandILX Calcs
Service soil pressure (D + L)3.296 ksf3.296
Largest negative moment, M at V = 0692.5 kip-ft692.5
φMn of 11 #8 top bars1274 kip-ft1274
One-way Vu at d from column 2 / φVc136.9 / 149.8 kips136.9 / 149.8
Transverse moment under column 2195.0 kip-ft195.0
Length for uniform pressure (suggestion)21.51 ft21.51