Unreinforced masonry wall

A one-foot strip of a concrete masonry wall or partition without reinforcement, spanning out of plane, loadbearing or not. The design keeps it uncracked: TMS 402-22 8.2 by allowable stress or 9.2 by strength, with the switch in the toolbar. Reinforced walls are the masonry wall out-of-plane calculation.

Edition. The design basis is TMS 402-22 / TMS 602-22. The text of the 2022 code is not on hand. Section numbers come from TMS's cross-reference and the free sample of the Masonry Designers' Guide 2022, which also confirms 8.2.6.2 and a value of Table 8.2.4.2; the wording was read in TMS 402-13. No 402-22 equation number is confirmed here: they are written as 402-13 numbers. The bed joint shear rows of the 2022 tables are the 402-13 values (to confirm against the code text).

Inputs of the unreinforced wall

  • Span: vertically (supported top and bottom, or a cantilever from the base) or horizontally between supports. A horizontal span uses tension parallel to the bed joints, gets no credit from axial load, and needs running bond.
  • Section: thickness; hollow units on face shell bedding, grouted at a spacing or fully; or solid units. The net section is at a bed joint: face shells only where hollow. Partial grouting interpolates the table by the share of grouted cells. Webs per unit and web thickness set the area for shear on the webs.
  • Wall weight: an input, counted as resisting tension. Enter what the wall weighs with its grout.
  • Check low dead load with a live lateral load: on by default. ASCE 7 has no combination for a live lateral load with dead load resisting; the MDG-2022 example takes 0.6D. This adds 0.6D + L in allowable stress and 0.9D + 1.6L in strength. Off uses the ASCE 7 combinations only, which credits the full dead load. Your judgment.
  • Use the lowest bed joint shear stress: off by default. The Guide's example takes the table's lowest value for out-of-plane sliding; off uses the row for the bond and grouting.
  • Loads: w the axial load per foot at the top, e from the wall centre line, p the out-of-plane pressure. Interior partitions: at least 5 psf (ASCE 7-22 4.3.4).
  • Deflection limit: span divided by the number entered; IBC Table 1604.3 by finish.

Auto-design (editor toolbar) varies thickness, grouting and grouted cell spacing. Objective: the thinnest wall, then the least grout. The wall weight is kept, so a heavier wall gets no credit until you enter it.

Checks performed

CheckAllowable stressStrength
Flexural tensionM/Sn − P/An against Table 8.2.4.2, 8.2.4.2ψ Mu/Sn − Pu/An against φ fr of Table 9.1.9.1, 9.2.4.1, φ = 0.60
Compressionfa/Fa + fb/Fb ≤ 1, 8.2.4.1 (402-13 Eq. 8-14)Pu/An + ψ Mu/Sn ≤ φ 0.80 f'm, 9.2.4.1
AxialP ≤ Pe/4 with the load's actual eccentricity (Eqs. 8-15, 8-19)φ Pn, 9.2.4.2 (Eqs. 9-11, 9-12)
Moment magnifierNone in the codeψ of 9.2.4.3, 1.0 at h/r up to 45
Axial tensionNot permitted, 8.2.5Not permitted, 9.2.5
Shear on the webs3/2 V/A ≤ 1.5 √f'm and 120 psi, 8.2.63.8 A √f'm and 300 A, 9.2.6
Shear on the bed joint3/2 V/An ≤ 37 or 60 psi + 0.45 Nv/An, or 15 psi, Table 8.2.6.256 or 90 An + 0.45 Nu, or 23 An, Table 9.2.6.1
DeflectionUncracked, against your limitSame

Stresses are checked at 41 stations along the height in every combination, so the wall's weight changing with height is captured. A cantilever takes an effective height of twice its height.

The drawings are the wall along its span and the wall at a bed joint.

Limitations

  • Out of plane only. In-plane shear wall action is not covered here.
  • Chapter 15 of 402-22, prescriptive partition walls, is new and only its contents are on hand: its height and length limits and anchorage rules are not checked. This calculation is the engineered route of the MDG example.
  • Concrete masonry. Clay masonry has a different modulus; AAC has its own chapter.
  • Masonry not laid in running bond spanning horizontally needs a continuous grout section, which is not modelled, so it is refused.
  • Parapets add weight; their own bending is not checked.
  • Stresses from restraint of movement are controlled by joints (8.2.2 commentary), not calculated.
  • φ of 0.60 and the numbers of the shear tables are 402-13 values (to confirm against the code text).

Verification examples

Verification status: 28 values compared in 6 examples (1 published, 5 hand calculations from the cited equations): 28 within tolerance, 0 recorded deviations. Thin: only 1 published example. Code basis: written from an older edition, with the differences noted. Not yet compared line by line with the target edition.

Published: Masonry Designers' Guide 2022, Example 11.3-1 (sample pp. 4-5; written to 402-22): section properties, stresses, allowable stresses and both shear limit states of a 12 ft hollow partition. The Guide checks midheight and gets 9.6 psi net tension. The wall's weight falls with height, so the largest net tension is a little higher up, 9.9 psi at 6.9 ft; ILX reports that, within the tolerance on the printed value. The margin against 12 psi is about the same.

Hand calculations: the same wall by strength design, bed joint strength, a grouted cantilever, a loadbearing wall's Fa, Fb, Pe and Pn, a horizontal span. There is no free published strength example of an unreinforced wall: MDG 12.3-1 to 12.3-3 are in the paid Guide.