Seismic nonstructural components

The horizontal seismic design force Fp on an architectural, mechanical or electrical component and its attachments by ASCE/SEI 7-22 Chapter 13, with the height factor Hf, the structure ductility factor Rμ, the component factors CAR and Rpo, the limits of Eqs. 13.3-2 and 13.3-3, the vertical force, the overstrength force for anchors, the anchor forces of a rigid component on four supports and the relative displacement DpI. It is an analysis: the result reads Calculated.

Inputs of the nonstructural component

  • Seismic hazard and structure: SDS; the seismic design category of the structure the component is in or on (13.1.2; it drives the Table 13.1-1 exemptions); the risk category of the structure (Ie of Table 1.5-2, used in Rμ and DpI); the seismic force-resisting system of the structure (R and Ω0 of Table 12.2-1 for Rμ, not specified or not listed for Rμ = 1.3, or entered; with several systems choose the one that gives the lowest Rμ); the average roof height h; and Hf by Eq. 13.3-4 with the approximate period Ta (Ct hn^x of Table 12.8-2 with hn taken as h, or entered: the lowest Ta of the two directions) or by Eq. 13.3-5 where the period is not known.
  • Component: the row of Table 13.5-1 (architectural) or Table 13.6-1 (mechanical and electrical components, vibration-isolated components, equipment support structures and platforms, distribution system supports and distribution systems) giving CAR (at or below grade plane, or above grade plane by a structure), Rpo and Ω0p, or entered values. For vibration-isolated rows, the restraint air gap over 0.25 in. doubles the design force (Table 13.6-1 note a). The component importance factor Ip (13.1.3: 1.5 for life-safety components such as sprinklers and egress stairs, hazardous contents, or Risk Category IV operation; yours), the operating weight Wp, where it is supported (above grade plane: Hf and Rμ apply; at or below grade plane: Hf = Rμ = 1.0 and the grade CAR), the height of the point of attachment z, and the CAR of a supporting platform (13.3.1.3: the component's CAR is not less than the platform's).
  • Anchorage: for a rigid component on four support points at the corners of an a × b rectangle, the spacings a and b, the height of the center of gravity above the attachments hcg and the number of anchors per support point.
  • Relative displacement: none, Eq. 13.3-10 from the height between attachments and the allowable drift ratio of Table 12.12-1, or Dp entered (Eq. 13.3-9 or 13.3-11).

Checks performed

CheckBasis
Height factor HfEq. 13.3-4, Hf = 1 + a1 (z/h) + a2 (z/h)^10 with a1 = 1/Ta ≤ 2.5 and a2 = 1 − (0.4/Ta)² ≥ 0, or Eq. 13.3-5, Hf = 1 + 2.5 (z/h); z/h ≤ 1.0; 1.0 at or below grade plane (13.3.1.1)
Ductility factor RμEq. 13.3-6, Rμ = (1.1 R / (Ie Ω0))^½ ≥ 1.3; 1.3 where the system is not specified or not listed; 1.0 at or below grade plane (13.3.1.2)
Component factorsCAR and Rpo (13.3.1.3, 13.3.1.4), Ω0p (13.4.2) from Tables 13.5-1 / 13.6-1; CAR not less than the platform's
FpEq. 13.3-1, Fp = 0.4 SDS Ip Wp (Hf / Rμ)(CAR / Rpo), not more than 1.6 SDS Ip Wp (Eq. 13.3-2) nor less than 0.3 SDS Ip Wp (Eq. 13.3-3); 2Fp for isolated components with an air gap over 0.25 in.
Vertical forceEv = 0.2 SDS Wp concurrent with Fp (13.3.1.6, Eq. 12.4-4a); Fp is QE with ρ = 1.0 (13.2.2)
Design forcesEh, Ω0p Eh (13.4.2, where the overstrength is required for anchors in concrete or masonry), 0.7 Eh for ASD (2.4, 13.1.8)
Anchorage forcesOverturning Eh hcg resisted by the support points: force along either side (M/2b, M/2a) or diagonally ((M/2)(cos θ/b + sin θ/a), θ = tan⁻¹(b/a), the FEMA P-2192 method); tension with (0.9 − 0.2 SDS)D (LRFD) or (0.6 − 0.14 SDS)D (ASD), compression with (1.2 + 0.2 SDS)D or (1.0 + 0.14 SDS)D; shear Eh / 4; with and without Ω0p
Relative displacementEq. 13.3-10, Dp = (hx − hy) ΔaA / hsx, or entered; DpI = Dp Ie (Eq. 13.3-8)
ExemptionsThe Table 13.1-1 row that may exempt the component (SDC A; SDC B; SDC C to F weight, attachment and Ip conditions), named for you to confirm

The drawings show the building elevation (schematic) with the attachment height z and the roof height h, and the component elevation (schematic outline: its size is not an input) with the center of gravity, the design force and the gravity and vertical force, the support spacing, hcg and the anchor forces.

Limitations

  • Components of 20 % or more of the combined effective seismic weight (13.1.1, 13.2.9) and Eq. 13.3-7 (accelerations from a nonlinear response history analysis) are outside this calculation.
  • The anchor design itself (ACI 318-19 Chapter 17 with the 17.10 seismic requirements, TMS 402 for masonry, ACI 355.2 qualification of post-installed anchors), prying (13.4.3), friction clips and power-actuated fasteners (13.4.5, 13.4.6) are yours; use the concrete anchor calculation for anchors in concrete.
  • The anchorage forces assume a rigid component on four support points; flexible components, more support points, isolator snubbers and their supporting frames are not analysed.
  • The design of the component, its support structure or platform, distribution system braces and hangers is not part of the calculation; the force on a brace is Fp of the tributary weight entered as Wp.
  • The 13.2.9 expression for a combined system is garbled in the text copy on file (to confirm against the code text); it is not used.

Verification examples

Verification status: 77 values compared in 18 examples (15 published, 3 hand calculations from the cited equations): 77 within tolerance, 0 recorded deviations. Code basis: the provisions it uses were read in the target edition.

FEMA P-2192-V1 (2020 NEHRP Provisions Design Examples, Chapter 8) works its examples with the ASCE 7-22 equations. FEMA prints Hf, Rμ and the coefficients rounded and multiplies with the unrounded values; periods are compared to 0.01 s.

ExampleWhat it checksPublishedILX Calcs
8.3-PANELPrecast spandrel panel, steel SMF building, z/h = 40.5/67.5, SDS 1.487 (pp. 339 to 349)Ta 0.81 s, a1 1.23, a2 0.76, Hf 1.74 (2.50 by Eq. 13.3-5), Rμ 1.71, 0.403 Wp, max 2.379 / min 0.446 Wp, Fp 4,570 lb, Ev 3,047 lbsame
8.3-FASTENERSFasteners of the connecting system (CAR 2.8, Ω0p 1.0) (p. 350)1.129 Wp, Fp 11,568 lbsame
8.4Egress stair, Ip = Ie = 1.5, Ta of the braced frame and Rμ of the moment frame (pp. 370 to 378)Ta 0.484 s, Hf 2.03, Rμ 1.40 (1.48 SCBF), 0.582 Wp; flight 410 / landing 298 lb, Ev 141 / 103 lb; fasteners 1.280 Wp, 903 / 657 lb; DpI 2.52 in.same
8.5-FANHVAC fan on the roof, ordinary masonry walls, SDS 0.474 (pp. 383 to 388)Ta 0.29 s, a1 2.5, a2 0, Hf 3.5, Rμ 1.3, 0.357 Wp, Fp 1,072 lb, Ev 284 lb, Vu 268 lb, bolt force −409 lb (compression)same
8.5-ISOLATEDSame fan on spring isolators, 2Fp (pp. 390 to 393)0.864 Wp, Fp = Fp,max 2,275 lb, 2Fp 4,550 lb, tension 448 lb, compression 2,023 lb, Vu 1,138 lb; with Ω0p 1,237 / 1,991 lbsame
8.6Threaded piping and hot-rolled bracing on a BRBF roof, Ip 1.5 (pp. 405 to 416)Ta 0.38 s, Hf 3.5, Rμ 1.53, 1.508 Wp (24.7 / 47.8 plf), supports 0.914 Wp, longitudinal brace 2,318 lbsame
8.7Elevated vessel and its platform, CAR raised to 1.4 (pp. 432 to 444)Ta 0.353 s, Hf 2.52, Rμ 1.48, 0.762 Wp, Fp 3,808 lb, Ev 1,200 lb; platform 762 / 240 lbsame

FEMA's tension case "LC6" uses 1.2D − Ev, which is not an ASCE 7 combination; the program uses (0.9 − 0.2 SDS)D for uplift, and the LC7 tensions and LC6 compressions match. Hand calculations: a component at grade (Hf = Rμ = 1.0, grade CAR, Fp 4,800 lb), a structure system not specified with Eq. 13.3-5 (Hf 2.25, Rμ 1.3, Fp 775.4 lb) and ASD anchor forces (minimum Fp 1,200 lb, −145 lb, 210 lb), all exact.