Cold-formed steel rafter

A sloped lipped C-section rafter with the thrust at its heel and the ceiling joist or tie that resists it, to AISI S240-20 Section B4.2 and the AISI S100-16 North American Specification with Supplement S2-20, with ASCE 7-22 load combinations.

Inputs of the cold-formed steel rafter

  • Section: an SSMA designation or custom dimensions. Fy and Fu are yours. Nothing is added for cold work.
  • Roof geometry: horizontal span from plate to ridge, slope as rise in 12, a horizontal overhang, and the rafter spacing.
  • Ridge: a ridge board with a tie at the heel makes a three-hinged frame, and the tie takes the thrust. A structural ridge beam or bearing wall holds the ridge up, with no thrust.
  • Area loads: by load type, each on the slope, on the horizontal projection or normal to the roof. Normal is positive toward the roof, negative for suction. Both rafters of a pair take the same load, so enter the heavier side.
  • Point loads: vertical, placed horizontally from the plate.
  • Bracing: each flange braced by sheathing or at a spacing you enter. S240 B4.5(b) states what sheathing counts. The rotational restraint kφ is yours, from S240 Appendix 1; 0 means none.
  • Compression basis: continuously braced (S240 B4.2.2(b): Fn = Fy with E3, and distortional buckling) or discretely braced (Chapter E at your brace spacing). Tick the box when your braces also restrict flange rotation, which makes Lm the spacing.
  • Kx: on the sloped length from plate to ridge. It enters E2 and the amplifier B1.
  • Bearing: flange bearing with its length N, or a clip, which turns web crippling off.
  • Tie: section, steel, the net area ratio An/Ag (your judgment; 0.85 is prefilled and is not a code value), and the screws at the heel.
  • Deflection limits: span / n, on the length along the slope and on twice an overhang. 0 turns a check off.

Auto-design varies the section (lightest first) and the screws at the heel, and the yield stress when unlocked. Spacing, tie and loads are kept.

Checks performed

CheckBasis
Flexure, positive and negative momentS240 B4.2.3; S100 F2, F3
Distortional buckling in flexureS240 B4.2.3; S100 F4, Appendix 2 2.3.3.3
CompressionS240 B4.2.2; S100 E2, E3
Distortional buckling in compressionS240 B4.2.2; S100 E4, Appendix 2 2.3.1.3
TensionS240 B4.2.1; S100 D2, D3
ShearS240 B4.2.4; S100 G2
Web crippling at the plateS240 B4.2.5, B1.6; S100 G5
Compression and bending, with B1S240 B4.2.6; S100 H1.2, C1.2.1.1
Tension and bendingS240 B4.2.6; S100 H1.1
Bending and shear; bending and web cripplingS240 B4.2.7, B4.2.8; S100 H2, H3
DeflectionIBC 2021 Table 1604.3, limits entered
Tie in tension; heel screwsS100 D2, D3, J4.3

The perpendicular load components bend the rafter as a simple span along the slope. The parallel components and the end reactions give the axial force by statics at every station. With a ridge board, moments about the heel give the thrust H = R / sin(slope), where R is the perpendicular reaction at the ridge.

Limitations

  • The tie is at the heel. A raised tie is not built.
  • Both rafters take the same load. Unbalanced snow and wind on one side are your entry on the heavier side.
  • Web holes, bearing stiffeners and clips are not designed. The tie's bending under a ceiling load is a job for the cold-formed joist type.
  • Under net uplift the tie goes into compression and the ridge pulls apart: the force is reported, and its check is yours.
  • The rafter's net section is taken as the gross section in D3.
  • S240 B4.2.2(b) prints F4 (a flexure section) for the compression distortional check. This calculation reads it as E4, the compression section, and says so in its note.
  • The tie net area ratio is your judgment. The module does not derive it from the screw pattern.

Verification examples

Verification status: 17 values compared in 6 examples (3 published, 3 hand calculations from the cited equations): 17 within tolerance, 0 recorded deviations. Code basis: the provisions it uses were read in the target edition.

No published worked example of a cold-formed rafter is on disk. The AISI Framing Design Guide D110 would give one; it is on the list to buy.

  • Published section strengths: the SSMA Guide (2022) p. 11, Mal, Mad and Vag of three sections, read back through the module. They confirm the section strengths, not the rafter's statics or combined checks.
  • Hand calculations: three cases of statics, closed form: thrust, moment and axial force of a ridge board frame and a ridge beam rafter under plan and normal loads. No published value checks these.